- Equipment Name: NACT Automatic type CT ratio polarity tester
Function | High and low voltage secondary circuit of a current ratio, polarity , phase types, leakage current online monitoring ; transformer sides the current size , ratio -line monitoring |
Power source | DC6V alkaline batteries (1.5V AAA × 4) approximately 30 hours of continuous work |
Test methods | Clamp CT |
Transmission | Wireless transmission, transmission distance of about 30m straight line |
Display Mode | LCD: 128dots × 64dots; blue backlight function , suitable for dark places |
LCD Size | Display field : 44mm × 27mm |
Meter size |
Host : width height thickness 75mm × 170mm × 30mm Voltage tester : width height thickness 76mm × 255mm × 31mm Low Current Clamp : Width height thickness 63mm × 160mm × 23mm |
Jaw size |
Voltage tester : φ48mm Low current clamp : φ30mm |
Sampling rate | 2 times / sec |
Measuring range |
High voltage detector : 0.0mA ~ 1000A Low Current Clamp : 0.00mA ~ 10A |
Resolution | High voltage detector : 0.1mA; Low Current Clamp : 0.01mA |
Gearshift | Automatic gearshift |
Primary circuit test accuracy 23 ℃ ± 3 ℃, below 80% RH |
0.0mA~10.0A: ±1%±5dgt |
10.0A~49.9A: ±2%±5dgt | |
50.0A~199.9A: ±3%±5dgt | |
200A~600A: ±4%±5dgt | |
601A~1000A: ±5%±5dgt | |
Secondary circuit test accuracy 23 ℃ ± 3 ℃, below 80% RH |
0.00~10A: ±1%±5dgt |
Ratio | Three kinds of variables than the display : ( a secondary circuit measured current ratio ; commuted to the secondary circuit 5A ratio ; to the 10kV-YY transformer 10kV/380V commuted ratio ) , the maximum ratio of 1:1 ten million ( 1.0K7) |
Data storage | 3000 groups , press the HOLD key to keep the data and numbered storage automatically (not affact by replace the battery or a sudden brownout) |
Line Voltage | The following 60kV line test ( must be insulated with 5 lever operation ) |
Data Hold | Press HOLD to hold the data , HOLD symbol is displayed , press the HOLD button to cancel maintained |
Data checking | Press HOLD + POWER key to enter the Data Recall Mode |
Overflow Show | Overrange overflow function : "OL A" symbol is displayed |
No signal indication | When the host transmits a signal is not received prompt " No Signal" |
Automatic shutdown | About 15 minutes after the start , the meter will automatically shut down |
Battery voltage | When the battery voltage is lower than 4.8V, low battery symbol appears , replace the battery alert |
Instrumentation quality |
Host : 240g ( with battery ) High voltage detector : 335g ( with battery ) Low current clamp : 170g Instrument total mass : 12Kg ( including insulation rod and battery ) |
Outside interference | No particularly strong electromagnetic fields ; without 433MHz, 315 MHz co-channel interference |
Working temperature and humidity | -25℃~45℃;below 80%Rh |
Storage Temperature and Humidity | -10℃~60℃; below 70%Rh |
Insulating rod dimensions | φ32mm, 1m / section ( 5 standard ) , can be extended . |
Low current clamp wire length | Standard 2 m ( distance can be lengthened according to the site ) |
Dielectric Strength |
High voltage detector : AC100kV/rms ( Section 5 insulating rod with high current clamp clamp core ) Host and low-voltage current clamp : AC1000V/rms |
Structure | Drip Ⅱ type ( high voltage detector ) |
Safety Rules | IEC1010-1, IEC1010-2-032, Pollution degree 2, CAT Ⅲ (600V), IEC61326 (EMC standard ) |
Accessories | Clamp : 1 ; Receiver: 1 ; current clamp : 1 ; Disc : 1 ; RS232 communication cable : 1 ; meter box : 1 ; insulating rod ( 1 m ) : 5 ; batteries (LR03) : 8 |